VEGA VEGABAR 86 4 … 20 mA_HART - Operating Instructions User Manual

Page 70

Advertising
background image

70

11 Supplement

VEGABAR 86 • 4 … 20 mA/HART

45039-EN-131010

Time format

12 h/24 h

Time zone Ex factory

CET

Rate deviation max.

10.5 min/year

Measurement electronics temerature
Resolution

1 °C (1.8 °F)

Accuracy

±1 °C (1.8 °F)

Voltage supply
Operating voltage U

B

Ʋ Non-Ex instrument

9.6 … 35 V DC

Ʋ Ex-d instrument

9.6 … 35 V DC

Ʋ Ex-ia instrument

9.6 … 30 V DC

Ʋ Ex-d-ia instrument

15 … 35 V DC

Ʋ Ex-d-ia instrument with ship approval 15 … 35 V DC

Interpolation protection

Integrated

Permissible residual ripple - Non-Ex, Ex-ia instrument

Ʋ for U

N

12 V DC (9.6 V< U

B

< 14 V)

≤ 0.7 V

eff

(16 … 400 Hz)

Ʋ for U

N

24 V DC (18 V< U

B

< 35 V)

≤ 1.0 V

eff

(16 … 400 Hz)

Permissible residual ripple - Ex-d-ia instrument

Ʋ for U

N

24 V DC (18 V< U

B

< 35 V)

≤ 1 V

eff

(16 … 400 Hz)

Load resistor

Ʋ Calculation

(U

B

- U

min

)/0.022 A

Ʋ Example - Non-Ex instrument with

U

B

= 24 V DC

(24 V - 9.6 V)/0.022 A = 655 Ω

Potential connections in the instrument
Electronics

Not non-floating

Ground terminal

Galvanically connected with the process fitting

Electrical protective measures

Housing material

Version

IP-protection class

NEMA protection

Plastic

Single chamber

IP 66/IP 67

NEMA 4X/6P

Double chamber

IP 66/IP 67

NEMA 4X

Aluminium

Single chamber

IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)

NEMA 4X/6P
-

Double chamber

IP 66/IP 67
IP 66/IP 68 (0.2 bar)

NEMA 4X
NEMA 4X

Stainless steel, electro-

polished

Single chamber
Single chamber

IP 69K
IP 66/IP 68 (0.2 bar)

-
NEMA 4X/6P

Advertising