VEGA VEGABAR 86 4 … 20 mA - Operating Instructions User Manual
Page 55
55
11 Supplement
VEGABAR 86 • 4 … 20 mA
45506-EN-131010
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … 25 bar/0 … 2500 kPa
130 bar/13000 kPa
0 bar abs.
Nominal measuring ranges and overload capacity in psi
The specifications are only an overview and refer to the measuring cell. Limitations due to the
material and version of the process fitting as well as the selected pressure type are possible. The
specifications on the nameplate apply.
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
Gauge pressure
0 … +0.4 psig
+75 psig
-0.725 psig
0 … +1.5 psig
+225 psig
-2.901 psig
0 … +5 psig
+435 psig
-11.60 psig
0 … +15 psig
+510 psig
-14.51 psig
0 … +30 psig
+725 psig
-14.51 psig
0 … +150 psig
+1300 psig
-14.51 psig
0 … +300 psig
+1900 psig
-14.51 psig
Absolute pressure
0 … 1.5 psi
225 psig
0 psi
0 … 5 psi
435 psi
0 psi
0 … 15 psi
510 psi
0 psi
0 … 30 psi
725 psi
0 psi
0 … 150 psi
1300 psi
0 psi
0 … 300 psi
1900 psi
0 psi
Output variable
Output signal
4 … 20 mA
Range of the output signal
3.55 … 22.0 mA (default setting)
Signal resolution
0.3 µA
Failure signal current output (adjustable) Last valid measured value, ≥ 21 mA, ≤ 3.6 mA
Max. output current
21.5 mA
Starting current
Ʋ up to 5 ms after switching on
≤ 3.6 mA
Ʋ 5 ms up to 5 s after switching on
≤ 10 mA
Ʋ 5 s up to 10 s after switching on
Adjusted failure current
Load
see load under Power supply
Damping (63 % of the input variable),
adjustable
0 … 999 s
Indication value - DIsplay and adjustment module
2)
2)
The indication values can be assigned individually