4 switch-on phase – VEGA VEGAFLEX 83 4 … 20 mA_HART - four-wire Polished version User Manual

Page 26

Advertising
background image

26

5 Connecting to power supply

VEGAFLEX 83 • 4 … 20 mA/HART - four-wire

41840-EN-130314

Terminal

Function

Polarity

8

Function ground with installa-

tion according to CSA

power supply

4...20mA

active

passive

common

IS GND

5

1

/L

/N

2

+

( )

(-)

6 7

8

Fig. 16: Connection compartment with double chamber housing with low volt-

age

Terminal

Function

Polarity

1

Voltage supply

+/L

2

Voltage supply

-/N

5

4 … 20 mA output (active)

+

6

4 … 20 mA output (passive)

+

7

Mass - output

-

8

Function ground with installa-

tion according to CSA

5.4 Switch-on phase

After connecting the instrument to power supply or after a voltage

recurrence, the instrument carries out a self-check for approx. 30 s:

Internal check of the electronics

Indication of the instrument type, hardware and software version,

measurement loop name on the display or PC

Indication of the status message "F 105 Determine measured

value" on the display or PC

The output signal jumps to the set error current

As soon as a plausible measured value is found, the corresponding

current is outputted to the signal cable. The value corresponds to the

actual level as well as the settings already carried out, e.g. factory

setting.

Connection compartment

with low voltage

Advertising