4 rectify faults – VEGA VEGAFLEX 83 4 … 20 mA_HART - four-wire Polished version User Manual

Page 61

Advertising
background image

61

9 Diagnostics and service

VEGAFLEX 83 • 4 … 20 mA/HART - four-wire

41840-EN-130314

Code
Text mes-

sage

Cause

Rectification

S601
Overfilling

– Danger of vessel overfilling

– Make sure that there is no

further filling

– Check level in the vessel

The following table shows the error codes and text messages in the

status message "Maintenance" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

M500
Error with the

reset delivery

status

– With the reset to delivery

status, the data could not

be restored

– Repeat reset

– Load XML file with sensor

data into the sensor

M501
Error in the

non-active

linearization

table

– Hardware error EEPROM

– Exchanging the electronics

– Send instrument for repair

M502
Error in the

diagnosis

memory

– Hardware error EEPROM

– Exchanging the electronics

– Send instrument for repair

M503
Reliability too

low

– The echot/noise ratio is the

small for a reliable meas-

urement

– Check installation and

process conditions

– Clean the antenna

– Change polarisation direc-

tion

– Use instrument with higher

sensitivity

M504
Error on an

device inter-

face

– Hardware defect

– Check connections

– Exchanging the electronics

– Send instrument for repair

M505
No echo avail-

able

– Level echo can no longer

be detected

– Clean the antenna

– Use a more suitable

antenna/sensor

– Remove possible false

echoes

– Optimize sensor position

and orientation

9.4 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

Maintenance

Reaction when malfunc-

tions occur

Advertising