9 Diagnostics and service

VEGAFLEX 81 • 4 … 20 mA/HART - four-wire

41825-EN-130314

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Setup" must be carried out again or must

be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside the normal working hours on

seven days a week around the clock.
Since we offer this service worldwide, the support is in the English

language. The service itself is free of charge, the only costs involved

are the normal call charges.

9.5 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module

with respective Ex approval may be used.
If there is no electronics module available on site, the electronics

module can be ordered through the agency serving you. The electron-

ics modules are adapted to the respective sensor and differ in signal

output or voltage supply.
The new electronics module must be loaded with the default settings

of the sensor. These are the options:

In the factory

Or on site by the user

In both cases, the serial number of the sensor is needed. The serial

numbers are stated on the type label of the instrument, on the inside

of the housing as well as on the delivery note.
When loading on site, first of all the order data must be downloaded

from the Internet (see operating instructions manual "Electronics

module").

9.6 Exchanging the cable/rod

If necessary, the cable or rod (measuring part) of the probe can be

exchanged.
Loosen the rod or cable with a fork wrench, wrench size 7 (rod ø 8,

cable ø 2 and 4) or wrench size 10 (rod ø 12).
1. Loosen the rod or cable with a fork wrench applied to the flat

surface, provide counterforce with another fork wrench.

2. Unscrew the loosened rod or cable manually.
3. Insert the new measuring rod carefully by hand with a twisting

motion into the opening of the process fitting.

4. Continue screwing in the rod manually into the opening of the pro-

cess fitting.

5. Exert counterforce with the second fork spanner and tighten the

rod or cable on the flat surfaces with the following torque.
Rod ø 8, cable ø 2 and 4: 6 Nm (4.43 lbf ft)
Rod ø 12: 10 Nm (7.37 lbf ft)

Reaction after fault recti-

fication

24 hour service hotline

Exchanging the cable/rod