9 Diagnostics and service

VEGAFLEX 81 • 4 … 20 mA/HART - four-wire

41825-EN-130314

Fig. 34: Exchange cable or rod

Information:

Please keep the stated torque so that the max. tensile strength

remains.

The rod or cable of the probe can be shortened individually.

1. Mark the requested length with mounted measuring rod.
2. Cable: Loosen the pins on the gravity weight (hexagon 3)
3. Cable: remove the pins
4. Cable: Pull the cable out of the gravity weight
5. Shorten the cable/rod with a cut-off wheel or metal saw at the

marking. Take note of the specifications in the following illustration

when shortening the cable.

6. Cable with gravity weight: Shift the cable according to the drawing

into the gravity weight

7. Cable with gravity weight: Fasten cable with the pins, torque 7 Nm

(5.16 lbf ft)
Cable with centering weight: Fasten cable with the pins, torque

7 Nm (5.16 lbf ft) and fix the clamping part on the centering

weight.

8. Enter new probe length and then carry out a fresh adjustment

(see "Setup procedure, Carrying out min. adjustment - Carrying

out max. adjustment").

Shorten cable/rod