10 Supplement

VEGABAR 83 • Modbus and Levelmaster protocol

46295-EN-131107

Adjustment range of the min./max. adjustment relating to the nominal measuring range:

Ʋ Percentage value

-10 … 110 %

Ʋ Pressure value

-20 … 120 %

Adjustment range of the zero/span adjustment relating to the nominal measuring range:

Ʋ zero

-20 … +95 %

Ʋ span

-120 … +120 %

4)

Ʋ Difference between zero and span

max. 120 % of the nominal range

Recommended max. turn down

20 : 1 (no limitation)

Nominal measuring ranges and overload capability in bar/kPa
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-

terial and version of the process fitting are possible. The specifications on the nameplate apply.

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

Gauge pressure
0 … +0.1 bar/0 … +10 kPa

+15 bar/+1500 kPa

-1 bar/-100 kPa

0 … +0.4 bar/0 … +40 kPa

+30 bar/+3000 kPa

-1 bar/-100 kPa

0 … +1 bar/0 … +100 kPa

+35 bar/+3500 kPa

-1 bar/-100 kPa

0 … +2.5 bar/0 … +250 kPa

+50 bar/+5000 kPa

-1 bar/-100 kPa

0 … +10 bar/0 … +1000 kPa

+90 bar/+9000 kPa

-1 bar/-100 kPa

0 … +25 bar/0 … +2500 kPa

+130 bar/+13000 kPa

-1 bar/-100 kPa

-1 … 0 bar/-100 … 0 kPa

+35 bar/+3500 kPa

-1 bar/-100 kPa

-1 … +1.5 bar/-100 … +150 kPa

+40 bar/+4000 kPa

-1 bar/-100 kPa

-1 … +10 bar/-100 … +1000 kPa

+90 bar/+9000 kPa

-1 bar/-100 kPa

-1 … +25 bar/-100 … +2500 kPa

+130 bar/+13000 kPa

-1 bar/-100 kPa

-0.05 … +0.05 bar/-5 … +5 kPa

+15 bar/+1500 kPa

-0.2 bar/-20 kPa

-0.2 … +0.2 bar/-20 … +20 kPa

+20 bar/+2000 kPa

-0.4 bar/-40 kPa

-0.5 … +0.5 bar/-50 … +50 kPa

+35 bar/+3500 kPa

-1 bar/-100 kPa

Absolute pressure
0 … 0.1 bar/0 … 10 kPa

15 bar/1500 kPa

0 bar abs.

0 … 0.4 bar/0 … 40 kPa

30 bar/3000 kPa

0 bar abs.

0 … 1 bar/0 … 100 kPa

35 bar/3500 kPa

0 bar abs.

0 … 2.5 bar/0 … 250 kPa

50 bar/5000 kPa

0 bar abs.

0 … 10 bar/0 … 1000 kPa

90 bar/9000 kPa

0 bar abs.

0 … 25 bar/0 … 2500 kPa

130 bar/13000 kPa

0 bar abs.

Nominal measuring ranges and overload capacity in psi
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-

terial and version of the process fitting are possible. The specifications on the nameplate apply.

4)

Values less than -1 bar cannot be set.