6 bristol controlwave micro, Wiring plan, Parameter – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) enamel Modbus and Levelmaster protocol User Manual
Page 75
Advertising
75
11 Supplement
VEGAPULS 66 enamel • Modbus and Levelmaster protocol
41368-EN-121011
11.6 Bristol ControlWave Micro
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
2
3
13
45
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
1 +SV
RS
485 on COM1
2 RX-
5 RXT
6 TXT
3 TX-
4 GND
7 not used
8 not used
Fig. 50: Connection of VEGAPULS 66 to RTU Bristol ControlWave Micro
1 VEGAPULS 66
2 RTU Bristol ControlWave Micro
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
2 (FC4)
RTU Data Type
32-bit registers as 2 16-bit registers
Input Register Base Number
1
The basic number of the input registers is always added to the input register address of VEGAPULS
66.
Address 1303 must hence be entered as register address for 1302 for RTU Bristol ControlWave
Micro.
Advertising