6 Set up with the display and adjustment module

SOLITRAC 31 • Profibus PA

43834-EN-131119

In menu item "Scaling unit" you define the scaling variable and the

scaling unit for the pulse rate on the display, e.g. volume in percent.

In menu item "Scaling" you define the scaling format on the display

and the scaling of the measured values for 0 % and 100 %.

Measured value min.

Measured value max.

To damp process-dependent measured value fluctuations, you can

set a time of 0 … 999 s in this menu item.

The default setting is a damping of 0 s.

In this menu item you can adjust the damping of the sensor. With

it you can suppress fluctuations in the measured value indication,

caused e.g. by an agitated product surface. This time can be between

1 and 1200 seconds. Keep in mind that the reaction time also in-

creases and the instrument reacts to quick level changes with a delay.

Generally a time of approximately 60 seconds is sufficient to smooth

the measured value indication.
With the setting "Automatic", the instrument itself calculates a suitable

damping on the basis of the adjustment and the measured value

changes. This setting is particularly suitable for application where fast

and slow level changes occur.

Setup - AI FB1 - Scaling

unit

Setup - AI FB1 - Scaling

Setup - AI FB1 - Damping

Setup - Damping