6 Set up with the display and adjustment module
SOLITRAC 31 • Profibus PA
43834-EN-131119
In menu item"Channel" you determine which measured value the
output refers to.
In menu item "Scaling unit" you define the scaling variable and the
scaling unit for the pulse rate on the display, e.g. volume in percent.
In menu item "Scaling" you define the scaling format on the display
and the scaling of the measured values for 0 % and 100 %.
Measured value min.
Measured value max.
To damp process-dependent measured value fluctuations, you can
set a time of 0 … 999 s in this menu item.
The default setting is a damping of 0 s.
In this menu item you can select which mode the sensor should oper-
ate in.
You can choose between overfill and dry run protection.
The relay outputs of the sensor react accordingly.
Overfill protection = the relay will deenergise (safe condition) when
the max. level is reached.
Dry run protection = the relay will deenergise (safe condition) when
the min. level is reached.
Setup - AI FB1 - Channel
Setup - AI FB1 - Scaling
unit
Setup - AI FB1 - Scaling
Setup - AI FB1 - Damping
Setup - Relay