4 Mounting
VEGABAR 83 • Slave sensor for electronic differential pressure
45051-EN-131011
4.4 Level measurement
The master/slave combination is suitable for level measurement in a
pressurized vessel
Keep the following in mind when setting up the measuring system:
•
Mount the master sensor below the min. level
•
Do not mount the master sensor close to the filling stream or
emptying area
•
Mount the master sensor so that it is protected against pressure
shocks from the stirrer
•
Mount the slave sensor above the max. level
1
2
Fig. 10: Measurement setup, level measurement in pressurized vessel
1 VEGABAR 83
1 VEGABAR 83 - Slave sensor
4.5 Differential pressure measurement
The master/slave combination is suitable for differential pressure
measurement
Take note of the following instructions for the measurement setup, for
example in gases:
•
Mount the instruments above the measuring point
Possible condensation can then drain off into the process line.