5 Connecting to power supply

VEGABAR 83 • Slave sensor for electronic differential pressure

45051-EN-131011

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

The voltage supply and the signal transmission are carried out via the

four-wire, screened connection cable from the master sensor.
You can find the data for this signal circuit in chapter "Technical data".

With plastic housing, the NPT cable gland or the Conduit steel tube

must be screwed without grease into the threaded insert.
Max. torque for all housings see chapter "Technical data".

5.2 Connecting

The voltage supply and signal output are connected via the spring-

loaded terminals in the housing.
The connection to the display and adjustment module or to the inter-

face adapter is carried out via contact pins in the housing.
Information:

The terminal block is pluggable and can be removed from the

electronics. To do this, lift the terminal block with a small screwdriver

and pull it out. When reinserting the terminal block, you should hear it

snap in.

Proceed as follows:
1. Unscrew the housing cover
2. If a display and adjustment module is installed, remove it by turn-

ing it slightly to the left.

3. Loosen compression nut of the cable entry
4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

1 cm (0.4 in) of insulation from the ends of the individual wires

5. Insert the cable into the sensor through the cable entry

Safety instructions

Voltage supply

Cable gland ½ NPT

Connection technology

Connection procedure