2 Mounting
VEGAWELL 52 • Service tanks (fuel, coolant)
41957-EN-130626
2 Mounting
2.1 Lateral installation
If there are high temperatures in the vessel, +80 … +110 °C
(+176 … +230 °F), mount VEGAWELL 52 laterally.
X
1
2
Fig. 4: VEGAWELL 52 - lateral mounting with shut-off valve
1 Heating system - Temperature: approx. +110 °C (+230 °F)
2 VEGAWELL 52 - laterally mounted - Temperature: max. +80 °C (+176 °F)
x Offset
Note:
Check if the permissible process temperature of the sensor is suitable
for your application.
Gauge pressure in the vessel influences the measured value. For that
reason there must be a pressure compensation facility in the vessel.
Heating in the vessel
Pressure compensation