Note:

Wherever the sensor displays a constant value, the reason could

also be the fault setting of the current output to "Hold value"

In case of a too low level indication, the reason could be a line

resistance that is too high

Measurement error with constant level

Fault description

Error pattern

Cause

Rectification

1. Measured value

shows a too low or too

high level

Leve

l

time

0

– Min./max. adjustment not

correct

– Adapt min./max. adjustment

– Wrong linearization curve

– Adapt linearization curve

– Running time error (small

measurement error close to

100 %/serious error close to

0 %)

– Repeat setup

2. Measured value

jumps towards 100 %

Level

time

0

– Due to the process, the ampli-

tude of the product echo sinks

– A false signal suppression was

not carried out

– Carry out a false signal sup-

pression

– Amplitude or position of a

false signal has changed (e.g.

buildup); false signal suppres-

sion no longer matches

– Determine the reason for the

changed false signals, carry out

false signal suppression, e.g.

with buildup

Measurement error during filling

Fault description

Error pattern

Cause

Rectification

3. Measured value re-

mains in the area of the

bottom during filling

Leve

l

time

0

– Echo from the probe end larger

than the product echo, for

example, with products with

ε

r

< 2.5 oil-based, solvents, etc.

– Check parameter "Medium"

and "Vessel height", adapt if

necessary

4. Measured value re-

mains momentarily

unchanged during fill-

ing and then jumps to

the correct level

Level

time

0

– Turbulence on the product

surface, quick filling

– Check parameters, change if

necessary, e.g. in dosing ves-

sel, reactor

5. Measured value

jumps sporadically to

100 % during filling

Leve

l

time

0

– Changing condensation or

contamination on the probe

– Carry out a false signal sup-

pression

6. Measured value

jumps to ≥ 100 % or

0 m distance

Leve

l

time

0

– Level echo is no longer

detected in the close range

due to false signals in the close

range. The sensor goes into

overfill protection mode. The

max. level (0 m distance) as

well as the status message

"Overfill protection" are output-

ted.

– Eliminate false signals in the

close range

– Check installation conditions

– If possible, switch off the func-

tion "Overfill protection"