9 Diagnostics and service

VEGAFLEX 83 • Foundation Fieldbus

44224-EN-130910

Fig. 51: Exchanging the measuring rod

Information:

Please keep the stated torque so that the max. tensile strength

remains.
7. Enter new probe length and if necessary the new probe type and

then carry out a fresh adjustment (see "Setup procedure, Carry-

ing out min. adjustment - Carrying out max. adjustment").

9.7 Software update

The following components are required to update the sensor soft-

ware:

Sensor

Voltage supply

Interface adapter VEGACONNECT

PC with PACTware

Current sensor software as file

You can find the actual sensor software as well as detailed infor-

mation of the procedure under "www.vega.com/downloads" and

"Software".
You can find information about the installation in the download file.