5 setup, 1 setup preparations, 2 setup steps – VEGA VEGAFLEX series 80 Electronics module User Manual

Page 10

Advertising
background image

10

5 Setup

Electronics module • VEGAFLEX series 80

43656-EN-121113

5 Setup

5.1 Setup preparations

If you have ordered the electronics module by stating the sensor

serial number, it is ready for the setup steps after installation and

connection to power supply.

If you have ordered the electronics module without stating the sen-

sor serial number or you are using a suitable electronics module

from stock, you first have to load the sensor data after installation.
Move via www.vega.com to the item "serial number search". The

order data of the sensor will be displayed after entering the serial

number.
Below the order data you will find "Sensor data for Service-DTM" as

XML file. This file includes all sensor-specific parameters as well as

the data of the factory setting.
Load this file with "Save target as" on your PC. Start PACTware and

under "Instrument data" go to the menu item "Additional functions",

then to "Electronics exchange". Transfer the XML file to the sensor.

5.2 Setup steps

If the instrument is used in the same application after the electronics

exchange, the previous parameter adjustment of the instrument must

be restored. For this purpose, you can use the import function of the

adjustment software PACTware with the device DTMs or the copy

function of the indicating and adjustment module.
Information:

It is recommended to recreated an existing false signal suppression

after an electronics exchange. If this is not possible, for example,

because the vessel is filled, the false signal suppression can be

imported also via the DTM. However, the false signal suppression

should be updated or recreated next time when the vessel is empty.

With sensor serial num-

ber

Without sensor serial

number

Parameter adjustment

Advertising