7 Setup with PACTware

WEIGHTRAC 31 • Foundation Fieldbus

42375-EN-131120

Fig. 25: Select inputs

Summation

If you want to use several instruments, for example on a broad con-

veyor belt, activate the function "Summation".
The instrument then operates as master of a cascading group.
X-ray alarm

Radiation from external sources can influence the measuring result of

the sensor.
Possible external radiation sources can be, for example, a weld joint

test on a neighbouring facility or other radiation-based instruments.
For this you need an additional sensor (X-ray alarm sensor) for detec-

tion of the external radiation.
The X-ray alarm is only outputted for the period of increased external

radiation. Then the X-ray alarm is automatically reset.
In this menu item you can determine the behaviour of the sensor

when external radiation sources appear. You can also select the

switching threshold as needed in case of external radiation.
You can choose whether the sensor should output modulated current

(dithering) or the set fault current in case external radiation appears.
In the case of modulated measuring current (dithering), the last

valid current value is maintained and the current output modulates a

square-wave voltage ±1 mA around this value.
Information:

If you have activated the X-ray alarm, you have to enter in the next

step the type and the data of the connected X-ray alarm sensor.