As an alternative, sensors with guided microwave can be used. These
are unaffected by foam generation and are best suited for such
applications.

When using a surge pipe in a vessel, influences from vessel
installations and turbulences can be excluded. Under these prereq-
uisites, the measurement of products with low dielectric values (ε

r

value ≥ 1.6) is possible. In very adhesive products, measurement in a
surge pipe is not recommended.

1

2

3

100%

4

5

8

6

7

0%

9

Fig. 16: Configuration surge pipe

1

Radar sensor

2

Marking of the polarisation direction

3

Thread or flange on the instrument

4

Vent hole

5

Holes

6

Weld joint

7

Welding neck flange

8

Ball valve with complete opening

9

Fastening of the surge pipe

Instructions for orientation:

l

Note marking of the polarisation plane on the sensor

Measurement in a surge
pipe

VEGAPULS

61 • Approval according to LPR radio standard

21