nzoom": Reset the presentation to the nominal measuring range

with single magnification

The following circumstances cause interfering reflections and can
influence the measurement:

l

High sockets

l

Vessel installations such as struts

l

Agitators

l

Buildup or welded joints on vessel walls

Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account for level
measurement.

This should be done with a low level so that possible interfering
reflections can be detected.

Proceed as follows:

1

Select the menu item "Additional settins" with [->] and confirm with
[OK]

. With [->] you have to select the menu item "False signal

suppression" and confirm with [OK].

2

Confirm again with [OK].

3

Confirm again with [OK].

4

Confirm again with [OK] and enter the actual distance from the
sensor to the product surface.

5

All interfering signals in this section are detected by the sensor
and stored after confirming with [OK].

Further settings/False
signal suppression