Compression flange DN 80

5 Nm (3.689 lbf ft)

-

Adapter flange DN 100

7 Nm (5.163 lbf ft)

Max. torque for NPT cable glands and Conduit tubes

-

Plastic housing

10 Nm (7.376 lbf ft)

-

Aluminium/Stainless steel housing

50 Nm (36.88 lbf ft)

Input variable

Measured variable

The measured quantity is the distance between
process fitting of the sensor and product surface.
The reference plane is the seal surface on the
hexagon or the lower side of the flange.

3

4

2

1

Fig. 49: Data of the input variable

1

Reference plane

2

Measured variable, max. measuring range

3

Antenna length

4

Useful measuring range

Max. measuring range

35 m (114.8 ft)

Recommended measuring range

up to 20 m (65.62 ft)

Output variable

Output signal

digital output signal, format according to IEEE-754

Sensor address

126 (default setting)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Profibus PA profile

3.02

Number of FBs with AI (function blocks with
analogue input)

3