4 Mounting

VEGABAR 86 • Slave sensor for electronic differential pressure

45052-EN-131011

1

2

h

0,8

1,0

Fig. 8: Measurement setup with interface measurement, h = distance between

the two measuring points
1 VEGABAR 86

2 VEGABAR 86 - Slave sensor

The interface measurement is possible in open as well as in closed

vessels.

4.6 Density measurement

With the Master/Slave combination also a density measurement can

be realised.
Requirements for a functioning measurement are:

Vessel with changing level

Product with consistent density

Distance between the measurement points as large as possible

Level always above the upper measuring point

Measurement setup