5 Connecting to power supply

VEGABAR 86 • Slave sensor for electronic differential pressure

45052-EN-131011

Fig. 12: Connection steps 5 and 6

6. Insert the wire ends into the terminals according to the wiring plan
Information:

Solid cores as well as flexible cores with wire end sleeves are insert-

ed directly into the terminal openings. In case of flexible cores without

end sleeves, press the terminal from above with a small screwdriver;

the terminal opening is freed. When the screwdriver is released, the

terminal closes again.
You can find further information on the max. wire cross-section under

"Technical data/Electromechanical data"
7. Check the hold of the wires in the terminals by lightly pulling on

them

8. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation

9. Tighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

10. Reinsert the display and adjustment module, if one was installed
11. Screw the housing cover back on
The electrical connection is hence finished.