7 Set up with the display and adjustment module

POINTRAC 31 • 8/16 mA/HART - four-wire

43388-EN-131119

This menu item appears only if you have selected under adjustment

mode (setup/adjustment mode) the "Two-point adjustment".
In this menu item you can set the min. pulse rate (ct/s) at which the

sensor should switch over.
Fill the vessel until the POINTRAC 31 is covered.
You thus get the min. pulse rate (ct/s) for the "covered" adjustment.
Enter the requested pulse rate manually or let the rate be determined

by POINTRAC 31. Automatic determination of the pulse rate should

be given preference.

You can enter the adjustment point (ct/s) manually.

You can let the adjustment point be determined by POINTRAC 31.

This menu item appears only if you have selected under adjustment

mode (setup/adjustment mode) the "Two-point adjustment".
In this menu item you can set the max. pulse rate (ct/s) at which the

sensor should switch over.
Empty the vessel until the POINTRAC 31 is uncovered.
You thus get the max. pulse rate (ct/s) for the "uncovered" adjustment.
Enter the requested pulse rate manually or let the rate be determined

by POINTRAC 31. Automatic determination of the pulse rate should

be given preference.

You can enter the adjustment point (ct/s) manually.

Adjustment "covered"

(two-point adjustment)

Adjustment "uncovered"

(two-point adjustment)