3 Product description

POINTRAC 31 • 8/16 mA/HART - four-wire

43388-EN-131119

Software from 1.6.0

Modification status electronics from -07

The instrument is available in different electronics versions. Each ver-

sion can be identified via the product code on the type label:

Standard electronics type PT30E-XX

The scope of delivery encompasses:

Radiation-based sensor

Mounting accessory

Documentation

– this operating instructions manual

– Safety Manual (SIL) PROTRAC series 30 (Document-ID 42961)

– Operating instructions manual "Display and adjustment mod-

ule" (optional)

– Ex-specific "Safety instructions" (with Ex versions)

– if necessary, further certificates

3.2 Principle of operation

The instrument is suitable for applications in liquids and bulk solids in

vessels under difficult process conditions. There are application pos-

sibilities in nearly all areas of industry.
The limit level is detected contactlessly through the vessel wall. Nei-

ther a process fitting nor a vessel opening is required. The instrument

is thus ideal for retrofitting.

In radiation-based measurement, a Caesium-137 or Cobalt-60 iso-

tope emits focussed gamma rays that are attenuated when penetrat-

ing the vessel wall and the medium. The PVT detector on the opposite

side of the tank receives the radiation. When the intensity of the

radiation drops below a defined value, e.g. due to damping, then the

POINTRAC 31 switches. The measuring principle has proven itself

well under extreme conditions because it measures contactlessly

from outside through the vessel wall. The measuring system ensures

maximum safety, reliability and plant availability independent of the

medium and its properties.

3.3 System limitations

There are several measuring principle-specific factors which can influ-

ence the measuring result. Keep these factors in mind in order to fully

utilize the capabilities of the instrument with respect to measurement

certainty and reproducibility.

The implemented radioactive isotope and its activity must be selected

according to the properties of the vessel and the medium. The neces-

sary radioactive activity must be calculated on the basis of the plant

data.

Electronics versions

Scope of delivery

Application area

Functional principle

Activity of the source