VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) HART and accumulator pack User Manual

Page 36

Advertising
background image

36

6 Set up with the indicating and adjustment module

VEGAPULS 66 • HART and accumulator pack

40933-EN-121011

higher the value, the more reliable the measurement. With a function-

ing measurement, the values are > 10 dB.

The "Echo curve" shows the signal strength of the echoes over the

measuring range in dB. The signal strength enables an evaluation of

the quality of the measurement.

The "False signal suppression" displays the saved false echoes (see

menu "Additional settings") of the empty vessel with signal strength in

"dB" over the measuring range.

A comparison of echo curve and false signal suppression allows a

more accurate conclusion on measurement reliability. The selected

curve is continuously updated. With the [OK] key, a submenu with

zoom functions is opened:

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Agitators

Buildup or welded joints on vessel walls

Diagnoses/Curve indica-

tion

Additional adjustments/

False signal suppression