background image

10

4 Mounting

VEGATOR 636 Ex • Signal conditioning instrument

45508-EN-130627

4 Mounting

4.1 General instructions

VEGATOR 636 Ex signal conditioning instrument with plug-in socket

for mounting on carrier rail according to EN 50022.

The front plate of VEGATOR 636 Ex can be provided with a lead-seal-

able transparent cover to protect the instrument against unauthorised

or inadvertent adjustment. See the following figure on how to remove

the transparent cover.

Fig. 2: Removing the transparent cover

For moisture-protected mounting outside the switching cabinet, we

offer an insulated protective housing with transparent cover (IP 65) for

surface mounting.
In this housing you can mount a maximum of 3 instruments of 36 mm

width.

4.2 Mounting instructions

The plug-in socket is constructed for carrier rail mounting according

to EN 50022. Operating voltage is connected to terminals 9 and 10.

For neighbouring signal conditioning instruments, it is possible to

continue connection L1 and N directly via the supplied bridges.
Danger:

The bridges must never be used with single instruments or at the end

of a row of instruments. If this rule is not heeded, there is a danger

of coming into contact with the operating voltage or causing a short

circuit.
A VEGATOR 636 Ex in Ex version is an auxiliary, intrinsically safe

instrument and may not be installed in explosion-endangered areas.

Installation place

Transparent cover

Housing IP 65

Installation