3 function chart – VEGA VEGATOR 636 Ex User Manual

Page 19

Advertising
background image

19

6 Setup

VEGATOR 636 Ex • Signal conditioning instrument

45508-EN-130627

A-mode

B-mode

2 Simulation an empty signal (approx. 1.5 s)
Level relay energised

Relay control lamp lights

Relay control lamp off

2 Simulation of an empty signal
Failure lamp

Failure lamp off

Failure lamp off

3 Simulation of a full signal (approx. 1.5 s)
Level relay deenergised

Relay control lamp off

Relay control lamp lights

3 Simulation of a full signal
Failure lamp

Failure lamp off

Failure lamp off

4 Return to the current operating condition (covered/

uncovered)

Check the process of the function test. Take the following criteria into

account for evaluation of the result:
Test passed

If all three switching conditions occur in the correct sequence and the

specified duration (±20 %), then the test is passed and the instrument

functions correctly.
Test not passed

The specified times deviate considerably from the table (>3 s)

One of the switching conditions remains unchanged

No start-up of the test - no signal sequence

6.3 Function chart

The following chart provides an overview of the switching conditions

depending on the set mode and the level.
The mode switch on the sensor (if available) must be set to max.

operation.

Sensor (max. opera-

tion)

Signal conditioning instrument

Mode on

the signal

condi-

tioning

instrument

Level

Signal

current -

Sensor

Sig-

nal lamp

- Switch-

ing output

(yellow)

Con-

trol lamp

- Failure

(red)

Outputs

Mode A
Overflow

protection

approx.

8 mA

Relay ener-

gized

transistor

conducts

Mode A
Overflow

protection

approx.

16 mA

Relay de-

energized

transistor

blocks

Evaluation