Ot_warn_limit (51h), Power_good_on (5eh), Ot_warn_limit (51h) power_good_on (5eh) – Rainbow Electronics MAX34440 User Manual

Page 30: Figure 1. power-supply sequencing

Advertising
background image

PMBus 6-Channel Power-Supply Manager

MAX34440

30

OT_WARN_LIMIT (51h)

The OT_WARN_LIMIT command sets the temperature, in degrees Celsius, of the selected temperature sensor at which
an overtemperature warning is detected. The 2 data bytes are in DIRECT format. In response to the OT_WARN_LIMIT
being exceeded, the device does the following:
1) Sets the TEMPERATURE bit in STATUS_BYTE.
2) Sets the TEMPERATURE and MFR bits in STATUS_WORD.
3) Sets the OT_WARN bit in STATUS_MFR_SPECIFIC.
4) Notifies the host through ALERT assertion (if enabled in MFR_MODE).

POWER_GOOD_ON (5Eh)

The POWER_GOOD_ON command sets the value of the output voltage that causes the PG output to assert. All enabled
power supplies must be above their associated POWER_GOOD_ON thresholds before the PG output is asserted.
All the enabled power supplies must also be above POWER_GOOD_ON for power-supply margining to begin. The
POWER_GOOD_ON level is normally set higher than the POWER_GOOD_OFF level and VOUT_UV_FAULT_LIMIT. The
2 data bytes are in DIRECT format.

Figure 1. Power-Supply Sequencing

TON_DELAY

OPERATION

COMMAND CODE OR

CONTROL PIN

PSEN PIN

(ACTIVE HIGH OR LOW/

OPEN DRAIN OR PUSH-PULL)

ADC INPUT

POWER_GOOD# BIT IN

STATUS_MFR_SPECIFIC

TON_MAX_FAULT_LIMIT

VOUT_UV_FAULT_LIMIT

TOFF_DELAY

POWER_GOOD_OFF

POWER_GOOD_ON