3 technical data, 1 standards, 2 environment – PowerWalker VFI 30000TP 3_3 BE User Manual

Page 13: 3 dimensional drawings

Advertising
background image

8

EN

W×D×H (mm)

3 Technical data

3.1 Standards

Product IEC62040-3:1999 and EN62040-3:2001

UPS VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI

Safety IEC62040-1:2008,EN62040-1:2003 and EN60950-1:2005

EMC IEC62040-2:2006 and EN62040-2:2005

3.2 Environment

0℃ ~ +40℃ (with batteries)

Working Temperature 0℃ ~ +40℃

Storage Temperature

Relative Humidity 5% ~ 90%, no condensation allowed

3.3 Dimensional drawings

Altitude derating coefficient See user operations section for more detail information

-30℃ ~ +65℃ (without batteries)

Vibration IEC68-2-6; max. 0.3mm (2 to 9Hz), max. 1m/s2 (9 to 200Hz) sinusoidal

Gross Weight (Kg)

UPS VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI

470*700*1752.5 Without package

974*743*2008 With package

195 Without batteries
515 With batteries
255 Without batteries

575 With batteries

Net Weight (Kg)

470*700*1752.5 Without package

974*743*2008 With package

195 Without batteries
515 With batteries
255 Without batteries

575 With batteries

UPS VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI

Advertising