Terminal block diagram

Warning!

High touch current earth connection essential before connecting supply.

2.If UPS rectifier input and bypass input are supplied from one mains only:
Connect the mains supply cables to the UPS rectifier input terminals L1, L2, L3, N and PE .
The following three jumpers must be fixed between the rectifier and bypass input terminals:
L1-L1, L2- L 2, L3- L3.