4 internal battery installation – PowerWalker VFI 30000TP 3_3 BE User Manual

Page 31

Advertising
background image

26

EN

Notice!

The following label must be displayed on all switching devices installed in the same
electrical system as the UPS, even when these are located at a distance from the area
in which it is located (according to European standard EN 62040-1).

Warning!

ENSURE THAT THE UNINTERRUPTIBLE POWER SYSTEM IS ISOLATED BE-
FORE WORKING ON THIS CIRCUIT.

5.4 Internal Battery Installation

Please complete the procedure below to install batteries:

1. Make sure that the breaker is in off position (Located in front of the unit).
2. Remove the eighteen screws on the battery cover and take off the battery cover (see Fig.1).

Fig. 1

breaker

REMARK:

THE FOLLOWING WARNINGS SHOULD BE OBSERVED DURING THE OPERATION:

-The batteries may contain potential electric shock danger because of high voltage.
-Wear safety goggles.
-Make sure to verify battery polarity before connecting.
-Make sure to keep wires away from the adjacent legs and sharp edges of shelves handles.