4.2.1 Speeds and Ramp Time Selections

Frequency Output Selection (Set Switches S1 and S2)

The minimum and maximum speeds are selected by setting the minimum output frequency and the
maximum output frequency. Switch S1 sets the maximum output frequency selection and Switch S2 sets the
minimum frequency selection. Table “A” is used for the 35Hz gearless motor and table “B” for the 100Hz
motor.

Table 8. Frequency Output Selection (Set Switches S1 and S2)

Switch
S1 / S2

SPEED TABLE A

MF06MK200 35 Hz Gearless Motor

SPEED TABLE B

MF06MK200 100Hz Motor

Minimum Speed

Maximum Speed

Minimum Speed

Maximum Speed

-1

-2

-3

-4

S2

switch

Trolley

Speed

fpm [m/min]

S1

switch

Trolley

Speed

fpm [m/min]

S2

switch

Trolley

Speed

fpm [m/min]

S1

switch

Trolley

Speed

fpm

[m/min]

0

0

0

0

8 Hz

26 [8]

35 Hz

121 [37]

29 Hz

20 [6]

100 Hz

66 [20]

0

0

0

1

9 Hz

29.5 [9]

19 Hz

66 [20]

14 Hz

10 [3]

50 Hz

33 [10]

0

0

1

0

13 Hz

46 [14]

22 Hz

75 [23]

23 Hz

16 [5]

62 Hz

43 [13]

0

0

1

1

4 Hz

13 [4]

20 Hz

69 [21]

10 Hz

6.5 [2]

54 Hz

36 [11]

0

1

0

0

15 Hz

53 [16]

28 Hz

95 [29]

32 Hz

20 [6]

80 Hz

53 [16]

0

1

0

1

5 Hz

16 [5]

21 Hz

72 [22]

12 Hz

6.5 [2]

58 Hz

40 [12]

0

1

1

0

6 Hz

20 [6]

23 Hz

79 [24]

16 Hz

10 [3]

66 Hz

43 [13]

0

1

1

1

7 Hz

23 [7]

25 Hz

85 [26]

18 Hz

13 [4]

70 Hz

46 [14]

1

0

0

0

19 Hz

66 [20]

41 Hz

141 [43]

50 Hz

33 [10]

115 Hz

75 [23]**

1

0

0

1

10 Hz

33 [10]

26 Hz

89 [27]

20 Hz

13 [4]

75 Hz

49 [15]

1

0

1

0

11 Hz

40 [12]

30 Hz

102 [31]

26 Hz

16 [5]

85 Hz

56 [17]

1

0

1

1

12 Hz

43 [13]

32 Hz

112 [34]

35 Hz

23 [7]

90 Hz

59 [18]

1

1

0

0

14 Hz

49 [15]

33 Hz

115 [35]

38 Hz

26 [8]

95 Hz

62 [19]

1

1

0

1

16 Hz

56 [17]

37 Hz

128 [39]

41 Hz

26 [8]

105 Hz

69 [21]**

1

1

1

0

17 Hz

59 [18]

39 Hz

135 [41]

44 Hz

29.5 [9]

110 Hz

72 [22]**

1

1

1

1

18 Hz

62 [19]

42 Hz

144 [44]

47 Hz

33 [10]

120 Hz

79 [24]**

)

Note: ** TMU VFD connected to a 50Hz power supply cannot achieve these speeds. These speeds are available
only from either 460v or 575v - 60Hz power supply.

Table 9. Example of Parameter Setting

EXAMPLE OF PARAMETER SETTING:
A 100Hz motor is connected to the inverter and 80Hz
maximum speed is desired. That speed is found on the 5

th

row of speed table B. The corresponding setting for S1
switches is in the same row to the left: 0-1-0-0 (off-on-off-
off).

ON

DIP

12

3
4

S1

Max speed set to 80Hz.