4.3 Fault Codes and Troubleshooting – TMU VFD

m

WARNING: Do not touch any circuit components while the main AC power is on. High voltages
are supplied to the inverter (including the programming switches). Wait for at least three
minutes after the supply voltage has been switched off before performing any service on the
unit. Failure to adhere to this warning can result in injury.

If the TMU VFD malfunctions, a fault lamp blinks on and off. The blinking pattern continues until a new fault
occurs or until power is switched off. The fault codes are explained in the table below.

Table 12. TMU VFD Fault Code Troubleshooting Guide

LED Color, Blinking Pattern

Possible cause.

What to do.

GREEN


Lower input voltage.

GREEN

Over voltage.

Supply voltage exceeds the specification

allows.

Deceleration ramp time is too short.

Extend Deceleration time.

GREEN

Stall supervision / over current.

Brake does not open properly or an

obstacle is on the track.

Incorrect motor dependent parameter setup.

Adjust air gap. Repair/replace brake.

Check that the motor parameter settings
(switch S4) match the motor(s) supplied.

GREEN

Deceleration ramp supervision.

Deceleration ramp has not been followed.

Supply voltage greater than specification

allows.

Reset to longer Deceleration ramp time.

Check voltage of all supply phases at

terminal X1.

GREEN

Inverter over temperature.

Motor current is too high (bearing problem,
obstacle on the track, brake does not open

properly).

Ambient temperature is too high.

Repair bearing problem. Remove

obstacle. Adjust air gap or repair or

replace brake.

Use a larger rated inverter.

GREEN

Under voltage.

Supply voltage < specification allows

Correct the input power supply problem.

Check for single-phase problem.

RED

Short circuit.

Break down in motor cable insulation.

Break down in motor winding insulation.

Inverter transistor failure.

Switch main power off.

Replace the motor cables.

Check motor resistance. Replace the

motor.

Replace inverter.

RED

Microprocessor fault.

Due to high electrical noise environment.

Switch power off for 10 seconds, then

back on.

)

Note: The latest active fault is always removed from the memory when power is switched off.

Drive will not run even though inverter is not in a fault condition:
y

Motor will not start if DC-bus voltage too high (above 745V), this occurs if any line-to-line voltage

exceeds 480V+5% = 504V. If line voltage cannot be reduced, install step-down transformer in inverter
branch circuit.

y

Check the supply voltage phases at terminal X1.

y

Check the control signals at terminal X1.

y

Check that the control voltage is correct. Rating plate is located on the left side of the inverter.

y

Check all parameter selections, especially the motor parameters (switch S4).

y

Check that the selected motor parameters (switch S4) correspond to the appropriate motor type.

y

Check that the microprocessor starts running. Both the green and red indicator LEDs blink once as the

inverter is powered up. After the one second initializing time, only the green LED should be lit.

y

Check that the brake opens and closes properly. Check the brake air gap.

y

Check plug connection for intermittent operations.