Vset, Rset, Iset – OSRAM OPTOTRONIC Constant current LED power supplies with 3DIM User Manual

Page 14

Advertising
background image

14

Vset

Rset

Iset

LEDset APPLICATIONS

Note 1: The E96 series covers a wide range of values. The

table contains only some sample values of this series. Please

check the standard E96 series to fi nd the value best suited

for meeting your current setting requirements.

Note 2: The values given above are calculated without con-

sidering the possible power and/or output voltage and/or

minimum output current limitations which depend specifi cally

on the output characteristics of the chosen ECG. Please

refer to the respective product datasheet.

Note 3: The resistor tolerance has an effect on the accuracy

of the current setting. Available standard tolerances are 5 %,

2 %, 1 %, 0.5 %, 0.25 % and 0.1 %. LEDset ECGs are de-

signed to provide up to 5 % of the overall control accuracy

(Rset – Iout) if Rset is a resistor with a tolerance of up to 1 %.

If higher than 1 %, the tolerance of Rset must be considered in

the Iout tolerance calculation.

Example:

This example is meant to help in choosing the most suitable commercial resistor for a given system.

The calculation applies to an OT 35/220-240/700 LTCS in LEDset confi guration to set an output current of 580 mA.

Starting from the basic relationship:

Therefore:

Looking at available values of commercial resistors (i.e. E96 series), 30.9 kΩ is the best choice.
The recalculated real current setting would be:

Note 4: Since the Iset current value is very low, the power

rating of the resistor is not an issue to be considered when

selecting the resistor (considering a maximum value of

50 kΩ

PRset = 3.8 mW).

Note 5: If the value of the commercial resistor differs too

much from the calculated resistance, connecting resistors in

series/parallel might help to obtain the precise required value.

Note 6: It is not recommended to set the Vset by dividing

the +12Vset voltage by a resistor divider. This setting is in

fact more complicated. Moreover, the stated accuracy toler-

ance of ±5 % for the overall control system may not be lon-

ger achieved because it is directly affected by the +12Vset

voltage tolerance which is ±10 %.

where Iout = 580 mA and Inom

max

= 700 mA

where Iset = 274 µA

and therefore Iout = 580.7 mA

Vset 1 + 9

8.33 V

Iout

Inom

Rset

30.87 kΩ

Vset

Iset

8.47 V