10

WIRING AND CONFIGURATION OF THE ECG

4.1.2. Control line – cable requirements
The maximum total cable length of a DALI

®

control line is

300 m. When selecting a cable, it must be ensured that the
voltage drop on the control line does not exceed 2 V at
250 mA.

The following table can be used as a quick reference guide
for selecting the correct cable cross-section.

Note: For reasons of clarity, it is recommended to use the
black and gray wire of the cable for the DALI

®

connection

(see fi gure 12).

Table 2: Recommended cable cross-sections

Cable length

up to 100 m

100 to 150 m

150 to 300 m

Cable cross-section

0.5 mm

2

0.75 mm

2

1.5 mm

2

Figure 13: Connection of multiple 3DIM ECGs via DALI

®

control line.

Figure 12: Individual wires of a DALI

®

control line.