Wiring and confi guration of the ecg, Led module hid lamp, Ot ecg pto ecg – OSRAM OPTOTRONIC Constant current LED power supplies with 3DIM User Manual

Page 9: Wiring and configuration of the ecg 4.1. dali, Digital addressable lighting interface

Advertising
background image

9

4. Wiring and confi guration of the ECG

WIRING AND CONFIGURATION OF THE ECG

4.1. DALI

®

– digital addressable lighting interface

4.1.1. Wiring
For DALI

®

operation, the 3DIM ECG (OPTOTRONIC

®

for

LED modules or POWERTRONIC

®

for HPD lamps) is con-

nected to the mains and to a DALI

®

controller or DALI

®

bus. The SD terminal is left unconnected. The LED module
or HPD lamp is connected to the output terminal of the
respective ECG.

Note: DALI

®

connection has to be considered at the inter-

face between luminaire head and pole.

Up to 64 DALI

®

electronic control gears can be controlled

via a 2-wire control line – individually, jointly or in up to
16 groups. All of them are connected in parallel to the
two wires (see chapter 4.1.2.). DALI

®

connections are not

polarized. Therefore, plus and minus poles do not have
to be checked.

The lighting can be switched and dimmed via the DALI

®

control line. Additional status information can be read out
and exchanged between the ECG and the control unit. The
type of status information that can be exchanged depends
on the ECG or the control unit.

More details about DALI

®

can be found at the following

websites (or in the corresponding standard IEC 62386):
www.osram.com/dali
www.osram.com/3dim

Figure 10: DALI

®

installation with OPTOTRONIC

®

3DIM ECG.

Figure 11: DALI

®

installation with POWERTRONIC

®

3DIM ECG.

OPTOTRONIC

®

3DIM ECG

POWERTRONIC

®

3DIM ECG

LED module

HID lamp

LED out

HID out

Lamp

Mains
50/60 Hz

Mains
50/60 Hz

DALI

®

bus/

DALI

®

controller

DALI

®

bus/

DALI

®

controller

L

L

LH

LL

N

N

SD

SD

DA

DA

DA

DA

OT ECG

PTo ECG

Advertising