OSRAM PrevaLED Core Z3 User Manual

Page 13

Advertising
background image

13

PrevaLED

®

Core Z3 LED modules

|

Electrical considerations

3.8 Maximum allowed number of control gears
per circuit breaker

The resistor has to be placed between Vset and GNDset:

DIP1

DIP2

Current

Off

Off

LEDset

Off

On

700 mA

On

Off

500 mA

On

On

350 mA

Please note:
To activate the LEDset interface, both DIP switches of the
LED module have to be in the “OFF” position.

For further information on the LEDset interface, please refer
to the LEDset application note at

www.osram.com

.

Example of wiring:

B16

B10

OTe 35/700

50

30

OT 35/LCTS

84

52

OT 45 LCTS

60

40

OT 45 DALI LCTS

47

18

OTe 25/CS

50

30

OTe 35/CS S

44

28

OTe 35/CS

25

15

OTe 50/1A4 CS

25

15

OTe 50/1A0 CS

25

15

OTe 50/CS FAN

25

15

OT FIT 15CS

28

17

OT FIT 25/CS

28

17

OT FIT 35/CS

28

17

OTi DALI 25

84*

52*

OTi DALI 35

60*

40*

OTi DALI 50 FAN

13

18

3.9 ESD

It is not necessary to handle PrevaLED

®

Core Z3 LED

modules in electrostatic protected areas (EPAs). To protect
a PrevaLED

®

Core LED module from electrostatic damage,

do not open it. The LED module fulfi lls the requirement of
the immunity standard IEC/EN 61547.

* Preliminary data

The following values result for the modules which are
possible to drive with LCTS drivers:

Module

I [mA] R [Ohm]

PL-CORE-2000-830 400

22419

PL-CORE-2000-840 385

21715

PL-CORE-2000-930 490

26642

PL-CORE-3000-830 590

31335

PL-CORE-3000-840 575

30631

PL-CORE-3000-930 730

Use DIP switch for 700 mA. Module is under-driven.

PL-CORE-5000-830 950

Use DIP switch for 700 mA. Module is under-driven.

PL-CORE-5000-840 885

Use DIP switch for 700 mA. Module is under-driven.