Description, Electrical operation, Automatic reset – GE Industrial Solutions Record Plus Motor Operator Mechanism: FC100 User Manual

Page 3: Manual operation, Figure 5. alignment of mounting brackets, Step 3 – operation description

Advertising
background image

4. Align the Mounting brackets parallel to each

other as shown in Figure 5.

5.

Align the breaker handle with the operator

mechanism, by adjusting the mechanism

position with the screw as shown in Figure 4

Close the operator and fasten the wing

screw [7]

Step 3 – Operation

Description

A motor Operated mechanism is designed to
open, close, and reset a circuit breaker by remote
control.
In an operating installation, the customer must

supply normally open ON and OFF push –

buttons, external wiring, a control power source

and any control circuitry.

Electrical Operation

With the breaker and operating mechanism in

their OFF positions, press ON button to energize

the motor, closing the breaker. When the breaker

handle reaches the ON position, an internal limit

switch disconnects the control circuitry.
When the OFF button is pressed, the motor is

energized, opening the breaker. After the breaker

handle reaches the OFF position, a limit switch de-

energizes the control circuit.
When the circuit breaker trips automatically, there

is no external trip indication, unless a separate bell

alarm accessory is provided to actuate a warning

device. It is necessary to press OFF to reset the

breaker.

Automatic Reset

For automatic reset, an auxiliary switch, available

as an accessory, returns the breaker to the

OFF/RESET position after it has tripped. The

switch is mounted inside the breaker and wired in

parallel with the OFF button. When the breaker

trips, the switch closes, moving the breaker handle

to OFF/RESET position. After the motor-operated

mechanism has reset the breaker, the limit switch

again opens the circuit. To use automatic reset,

the ON push – button must be SPDT type and

wired as in Figure 7. (The Auto/ Reset scheme

applies to AC devices only and is not applicable to

DC applications).

Manual Operation

Unscrew the wing nut and lift the operator to

disengage the handle and operate the breaker

handle. To return to electrical operation, align

the breaker handle with the operator mechanism

and close the operator and fasten the wing screw.
Figure 6 is the outline view of completed

installations with dimensions.

ACCESS TO SCREW, FOR

MECHANISM ADJUSTMENT

‘OFF’ SIDE

ALIGN BREAKER
HANDLE TO THIS

AREA

[4,5,8]

MOUNTING

BRACKET

[7]

Figure 4. Mounting of Motor Operating Mechanism on

Breaker


PARALLEL
ALIGNMENT

Figure 5. Alignment of mounting brackets