Table 3. electrical specifications, Electrical data – GE Industrial Solutions Record Plus Motor Operator Mechanism: FC100 User Manual

Page 4

Advertising
background image

Electrical Data

Table 3 contains the electrical specifications for
the motor operated mechanism.

Control Timing

(Sec)

Catalog

No.

Volts

In-Rush

Amps

Running

Amps

Closing Opening

Recommended

UL Listed Fuse

120V AC

10.5

5.0

FCEMF3

125V DC

13.5

4.0

240V AC

6.5

3.0

FCEMF6

250V DC

8.0

2.5

1 Amp

Time Delay

FCEMFF 24V AC

31.0

15.5

FCEMFG 48V DC

20.0

7.0

.15 .13

2 Amp

Time Delay

Table 3. Electrical Specifications

Figure 6. Outline view of completed installations with dimensions.