Accessory definitions, S12p, S13p – GE Industrial Solutions ZBTSD Series User Manual

Page 14: T3/w3

Advertising
background image

12

71R

-4000B

ZBTS / ZBTSD Operation & Maintenance Manual

Accessory Definitions

(cont’d)

R50

In Phase Monitor this feature restricts Live to Live Source
Transfers

to occur unless both Sources are within 7 electri-

cal degrees or less of each other. (live Source to live Source
transfers usually occur during transfer back to Source 1
or during Testing). R50 does not change the operation
of the Automatic Transfer Switch in a power failure mode.
After all timer functions have elapsed, the CHECKING
FOR SOURCE SYNCHRONISM

will be displayed as well

as the direction of transfer (S1-S2 for example denotes
transfer from Source 1 to Source2). When synchronism is
accomplished, transfer will take place.
Notes: - If S2 Frequency is less than S1 Frequency,

display will show a series of (- - - - -…..) symbols.

- If S2 Frequency is greater than S1 Frequency,

display will show a series of (+++++…..) symbols.

- Each (-) or (+) symbol represents 10 electrical

degrees out of phase. A maximum of 18 symbols
(180 electrical degrees) can be monitored.

- The number of (-) or (+) symbols decrease

as the two sources approach synchronism
and increase as the two sources drift out
of synchronism.

- If S1 and S2 Frequencies are identical, the

display will show a series of alternating

- - - -

symbols (++++…) which also indicate the
approximate out of phase degrees

In the event that the Sources do not come within 7
electrical degrees of each other within 60 seconds, the
unit will display the message: SYNCH CHECKING and
will allow the user to BYPASS. If the BYPASS button is
pressed, the unit will display the message: WARNING
MAY CAUSE DAMAGE TO THE LOAD

. Pressing XFR

will actually bypass the R50. Since R50 is a passive device,
the length of time it takes to reach Synchronism is de-
pendent on the frequency difference between the two
Sources. Source 1 is usually a Utility and the frequency
is not within the control of the consumer. Source 2
needs to be adjusted to create an adequate difference
in order for the transfer to happen a timely fashion.

Note: For optimum performance, Source 2

Generator should be adjusted a Maximum of
2 Hertz above or below the Utility frequency,
minimum of 0.1 Hertz. (58 to 59.9) or
(60.1 to 62) Hertz. Adjustment of Generator
to 60Hertz could cause lengthy transfer delay

.

R50 Feature can be turned ON or OFF via CFG Menu
(see page 17). Factory Default if OFF.

S5P

Auto / Semi Manual selector
In “Auto” position, retransfer to Source 1 is automatic
after the T timer has timed out. The T time delay is
bypassed if Source 2 fails. In “Manual”, retransfer to
Source 1 is upon depression of BYPASS DELAY button
YEN or if Source 2 fails.

S12P

Auto / Manual Selector
In “Auto” position, the Automatic Transfer Switch
functions automatically as specified with the Switch
drawings. In “Manual” the Automatic Transfer Switch will
transfer to either direction upon depression of Source 1
or Source 2 transfer buttons. Should Source 1 fail, the
Generator (Source 2), will automatically start. Once
transferred in Manual, the Switch maintains position
selected even if selected power fails.

S13P

Transfer Commit. Configured via CFG menu. (see page 17)
When this Feature is set to OFF: The transfer Switch is
not committed to transfer unless the outage duration is
longer than the timers that precede the transfer to
Source 2 position. This assumes that the outage will be
an isolated event. When this Feature is set to ON: The
transfer Switch is committed to transfer to Source 2
position once the W timer has begun timing, even if
Source 1 power returns before the transfer to Source 2.
This is to ensure that the transfer takes place, because
one outage may be followed by another.

S14

Test / Auto / Source 1 Selector, Door mount

SW1

Auto/Off/Start Engine control selector, Door mount
(Keyed or non-keyed operation available)

SW2

Auto / Off Engine control selector, Door mount
(Keyed or non-keyed operation available)

SW3

Source Priority Selector Switch, Door mount
Allows selection of Source 1 or Source 2 to be the Prime
Source. Transfer Switch will transfer to selected Prime
Source if that Source is available. (Keyed or non-keyed
operation available)

T

Time Delay (S1) Source 1 Stable Timer. To delay transfer
to Source 1 (immediate retransfer on Source 2 failure).
Adjustable 0-60 minutes in 1 second increments.
Standard setting is 30 minutes. Adjust via SET menu
(see page 18)

T3/W3

Elevator Pre-Signal Auxiliary Contacts: Open 0-60
seconds prior to transfer to either direction, re-closes
after transfer.

U

(S2) Source 2 Stop Delay Timer. Allows Engine to run
unloaded after switch retransfer to Source 1. Adjustable
0-60 minutes in 1 second increments. Standard setting is
5 minutes. Adjust via SET menu (see page 18)