Entelli-switch 250 controller, Lcd & keypad, Entelli-switch 250 – GE Industrial Solutions ZBTSD Series User Manual

Page 9

Advertising
background image

71R

-4000B

7

ZBTS / ZBTSD Operation & Maintenance Manual

Entelli-Switch 250 Controller

(cont’d)

LCD & Keypad

These options are accessible through the LCD and keypad
(see figure below). To become familiar with the options
loaded into a particular unit, scrolling through the SET
and CFG menu will show the descriptions of the options
(see pages 16-17). These menus are the very same menus
that are used to access the setting and/or configuration
of these options. The SET (setting) menu is primarily
used to show or change, time and voltage settings. The
CFG menu is primarily used to turn an option on or off.
When scrolling through these menus, no changes can be

made without entry of the access code. The factory set six-
digit access code is located on a white label on the back
of the unit (see figure 11 pgs. 16-18).

The Entelli-Switch 250 has many logic options. Each controller
is downloaded with options at the time of manufacture.
The collection of options that any one controller has is
specified at the time of order placement. The following
pages include all the options that can reside in the con-
troller. Not all units include all options.

Entelli-Switch 250

Entelli-Switch 250

S 1 O K

01 : 5 0

W E D 3 1 M AY 2 0 0 8

Source 2 (Red)
indicates Source 2
is acceptable for use

Source 1 LED (Green)
indicates Source 1 is
acceptable for use

Exercise Event
“Impending”

SET Menu

M O R E C F G T E ST S E T

#1 or the word on the LCD
above the key. The word above
the key changes depending on
which screen is being displayed.

#2 or the word on the LCD
above the key. The word above
the key changes depending on
which screen is being displayed.

#3 or the word on the LCD
above the key. The word above
the key changes depending on
which screen is being displayed.

#4 or the word on the LCD
above the key. The word above
the key changes depending on
which screen is being displayed.

Current Time,
Day and
Date of Display

Source 1 Position LED (Green)
indicates Power Panel (ATS)
is closed to Source 1 position

Source 2 Position LED (Red)
indicates Power Panel (ATS)
is closed to Source 2 position

Menus (

more, cfg, test

)

Keypad

* E *

LCD Screen

Figure 9

Advertising