Step 1 – unpack and inspect, Step 2 – breaker status, Step 3 – installation – GE Industrial Solutions Record Plus Shunt Trip and Undervoltage Release User Manual

Page 2

Advertising
background image

Voltage Shunt

Trip

UVR

Vac

Vdc

Cat. No.

Rating, mA

Cat. No.

Rating, mA

— 12

FASHTB

200 — —

24 24

FASHTD

150

FAUVRD 50

48 48

FASHTF 60 FAUVRF 20

110–130 110–125 FASHTJ

40

FAUVRJ

15

120 —

FASHTK 40

220–240

250

FASHTN 20 FAUVRN 15

277 —

FASHT7 11 FAUVR7 15

400–480

— FASHTU 20 FAUVRU 15

50 or 60 Hz.
Shunt trip suitable for use with ground-fault sensing and relaying equipment;

55% trip.

Table 1. Catalog numbers and ratings for Record Plus™ shunt trip and undervoltage release accessories.

Step 1 – Unpack and Inspect

Unpack the shunt trip or undervoltage release kit and

inspect it for shipping damage. Read the circuit breaker

installation instructions carefully. Insure that the circuit

breaker and the accessory have the proper ratings for

current, voltage, interruption, and contact duty; wire

routing; installation; and operation for the application.
Accessories with the catalog number suffix W are factory

equipped with #18 AWG wire leads, 36 inches long.

Shunt trip leads are black and undervoltage release

leads are blue.

Step 2 – Breaker Status

Either trip the circuit breaker by activating the red trip

button on the front of the breaker or move the breaker

handle to the

OFF

position, both shown in Figure 2.

Step 3 – Installation

1. Loosen, but do not remove, the captive screws

holding the accessory cover on the circuit breaker,

as shown in Figure 3 for an FB100 and FC100

breaker and in Figure 4 for an FE150 or FE250

breaker Figure 5 for an FG400/FG600 Breaker.

Remove the cover.

2. The shunt trip or undervoltage release snaps into

place in its designated pocket in the circuit

breaker, as illustrated in Figure 3, Figure 4 and

Figure 5. It can be easily removed by gently

prying from underneath with a small screwdriver.

Figure 2. (a) Tripping the breaker or (b) turning it OFF.

Figure 3. Installation in an FB100 and FC100 circuit breaker.

(a)

(b)

Figure 4. Installation in an FE150 or FE250 circuit breaker.

Advertising