Step 6 – Check Breaker

Functions

Perform operational checks to insure proper

functioning of the new accessory.

• For a shunt trip, apply the rated voltage and verify

that the breaker trips.

• For an undervoltage release, apply the rated

voltage to allow the breaker to close, then remove

the voltage and verify that the breaker trips.

See NEMA publication AB4 for further details.

WARNING

: It is important that the cover is installed

correctly to ensure proper circuit breaker operation.