Data sheet, Feature descriptions – GE Industrial Solutions EBVW020A0B Barracuda Series User Manual

Page 8

Advertising
background image

GE

Data Sheet

EBVW020A0B Barracuda Series; DC-DC Converter Power Modules

36-75Vdc Input; 12.0Vdc, 20.0A, 240W Output

July 22, 2013

©2012 General Electric Company. All rights reserved.

Page 8

Feature Descriptions

Overcurrent Protection

To provide protection in a fault output overload condition, the

module is equipped with internal current-limiting circuitry and
can endure current limiting continuously. If the overcurrent
condition causes the output voltage to fall greater than 4.0V

from V

o,set

, the module will shut down and remain latched off.

The overcurrent latch is reset by either cycling the input power
or by toggling the on/off pin for one second. If the output

overload condition still exists when the module restarts, it will
shut down again. This operation will continue indefinitely until

the overcurrent condition is corrected.
A factory configured auto-restart option (with overcurrent and
overvoltage auto-restart managed as a group) is also available.

An auto-restart feature continually attempts to restore the
operation until fault condition is cleared.

Remote On/Off

The module contains a standard on/off control circuit reference
to the V

IN

(-) terminal. Two factory configured remote on/off logic

options are available. Positive logic remote on/off turns the
module on during a logic-high voltage on the ON/OFF pin, and
off during a logic low. Negative logic remote on/off turns the

module off during a logic high, and on during a logic low.
Negative logic, device code suffix "1," is the factory-preferred
configuration. The On/Off circuit is powered from an internal

bias supply, derived from the input voltage terminals. To turn
the power module on and off, the user must supply a switch to

control the voltage between the On/Off terminal and the V

IN

(-)

terminal (V

on/off

). The switch can be an open collector or

equivalent (see Figure 15). A logic low is V

on/off

= -0.3V to 0.8V.

The typical I

on/off

during a logic low (Vin=48V, On/Off

Terminal=0.3V) is 147µA. The switch should maintain a logic-low
voltage while sinking 310µA. During a logic high, the maximum

V

on/off

generated by the power module is 8.2V. The maximum

allowable leakage current of the switch at V

on/off

= 2.0V is 10µA.

If using an external voltage source, the maximum voltage V

on/off

on the pin is 14.5V with respect to the V

IN

(-) terminal.

If not using the remote on/off feature, perform one of the
following to turn the unit on:
For negative logic, short ON/OFF pin to V

IN

(-).

For positive logic: leave ON/OFF pin open.

Figure 15. Remote On/Off Implementation.

Output Overvoltage Protection

The module contains circuitry to detect and respond to output
overvoltage conditions. If the overvoltage condition causes the
output voltage to rise above the limit in the Specifications Table,

the module will shut down and remain latched off. The

overvoltage latch is reset by either cycling the input power, or
by toggling the on/off pin for one second. If the output

overvoltage condition still exists when the module restarts, it
will shut down again. This operation will continue indefinitely
until the overvoltage condition is corrected.
A factory configured auto-restart option (with overcurrent and
overvoltage auto-restart managed as a group) is also available.
An auto-restart feature continually attempts to restore the
operation until fault condition is cleared.

Overtemperature Protection

These modules feature an overtemperature protection circuit to
safeguard against thermal damage. The circuit shuts down the

module when the maximum device reference temperature is
exceeded. The module will automatically restart once the
reference temperature cools by ~25°C.

Input Under/Over voltage Lockout

At input voltages above or below the input under/over voltage
lockout limits, module operation is disabled. The module will

begin to operate when the input voltage level changes to within
the under and overvoltage lockout limits.

Load Sharing

For higher power requirements, the EBVW020A0 power module
offers an optional feature for parallel operation (-P Option code).
This feature provides a precise forced output voltage load
regulation droop characteristic. The output set point and droop
slope are factory calibrated to insure optimum matching of
multiple modules’ load regulation characteristics. To implement
load sharing, the following requirements should be followed:

The V

OUT

(+) and V

OUT

(-) pins of all parallel modules must be

connected together. Balance the trace resistance for each
module’s path to the output power planes, to insure best load

sharing and operating temperature balance.

V

IN

must remain between 40V

dc

and 75V

dc

for droop sharing

to be functional.

It is permissible to use a common Remote On/Off signal to
start all modules in parallel.

These modules contain means to block reverse current flow

upon start-up, when output voltage is present from other
parallel modules, thus eliminating the requirement for

external output ORing devices. Modules with the –P option
will self determine the presence of voltage on the output
from other operating modules, and automatically increase its

Turn On delay, T

delay

, as specified in the Feature Specifications

Table.

When parallel modules startup into a pre-biased output, e.g.
partially discharged output capacitance, the T

rise

is

automatically increased, as specified in the Feature
Specifications Table, to insure graceful startup.

Insure that the load is <50% I

O,MAX

(for a single module) until

all parallel modules have started (load full start > module

T

delay

time max + T

rise

time).

If fault tolerance is desired in parallel applications, output
ORing devices should be used to prevent a single module
failure from collapsing the load bus.