Environmental specifications, Car1212dc series dc-dc converter, Data sheet – GE Industrial Solutions CAR1212DC series User Manual

Page 6: Input: -36v, Output: 12v, Or 5 v, Emc compliance

Advertising
background image

GE

Data Sheet

CAR1212DC series DC-DC converter

Input: -36V

D C

to -75V

DC

; Output: 12V

DC

@ 1200W; 3.3V

DC

or 5 V

DC

@ 1A

October 21, 2013

©2013 General Electric Company. All rights reserved.

Page 6

Environmental Specifications

Parameter

Min

Typ

Max

Units

Notes

Ambient Temperature

-10

6

70

°C

Air inlet from sea level to 5,000 feet.

Storage Temperature

-40

85

°C

Operating Altitude

2250/7382

m / ft

Non-operating Altitude

8200/30k

m / ft

Power Derating with Temperature

2.5

%/°C

51°C to 70°C

7

Operating Temperature Derating with

Altitude

2.0

°C/305 m

°C/1000 ft

Above 2250/7382 m/ft; 3962/13000 m/ft

max

Acoustic noise

55

dbA

25°C, half load

Humidity
Operating

Storage

30
10

95
95

%
%


Relative humidity, non-condensing

Shock and Vibration acceleration

6

Grms

NEBS GR-63-CORE, Level 3, 20 -2000Hz, min

30 minutes

Earthquake Rating

4

Zone

NEBS GR-63-CORE, all floors, Seismic Zone 4

Designed and tested to meet NEBS

specifications.

EMC Compliance

EMC

Parameter

Criteria

Standard

Level

Test

DC input

Conducted emissions

EN55022, FCC Docket 20780 part 15, subpart J
Telcordia GR1089-CORE, Class A

A

0.15 – 30MHz

Radiated emissions

EN55022

A

30 – 10000MHz

DC input

immunity

Voltage dips

EN61000-4-11

B

-30%, 10ms

B

-60%, 100ms

B

-100%, 5sec

Voltage surge

EN61000-4-5

A

2kV, 1.2/50µs, common mode

A

1kV, 1.2/50µs, differential

mode

Fast transients

EN61000-4-4

B

5/50ns, 1kV (common mode)

Enclosure

immunity

Conducted RF fields

EN61000-4-6

A

130dBµV, 0.15-80MHz, 80%

AM

Radiated RF fields

EN61000-4-3, level 3

A

10V/m, 80-1000MHz, 80% AM

ENV50140

A

ESD

EN61000-4-2, level 3

B

6kV contact, 8kV air


6

Designed to start at an ambient down to -40°C; meet spec after ≅ 30 min warm up period, may not meet operational limits below -10°C.

7

The maximum operational ambient is reduced in Europe in order to meet certain power cord maximum ratings of 70°C. The maximum

operational ambient where 70°C rated power cords are utilized is reduced to 60°C until testing demonstrates that a higher level is acceptable.

Advertising