Introduction

The Motor Operator Mechanism, shown in Figure 1, can
be installed in 800–4000 A frame Power Break® II circuit
breakers. It provides a means of remotely or
automatically charging the springs that close the breaker.
Table 1 lists the catalog numbers and corresponding
electrical data for the available models. Note that the
Remote Close and Shunt Trip accessories are not
included with the Motor Operator Mechanism; they must
be ordered separately.

Figure 1. Motor Operator Mechanism.

Remote Operation

The circuit breaker closing springs can be charged
remotely by shorting terminals 17 and 35 on the terminal
block on the right side of the breaker, with a push button
or similar device, for a minimum of five seconds. Power
for the Motor Operator must also be applied to terminals
18 and 36, as shown in the wiring diagram in Figure 6.

Automatic Operation

Connect terminals 17 and 35 on the terminal block on
the right side of the breaker with a jumper wire. The
Motor Operator will automatically recharge the breaker
closing springs whenever the breaker closes.

C

C

C

C A

A

A

A U

U

U

U T

T

T

T IIIIO

O

O

O N

N

N

N ::::

Do not wire breakers for both automatic

charge and automatic close.

A

A

A

A T

T

T

T T

T

T

T E

E

E

E N

N

N

N T

T

T

T IIIIO

O

O

O N

N

N

N ::::

Ne pas câbler les disjoncteurs pour

tous les deux l’armement automatique et la fermeture
automatique.

Control

Rated Voltage

(50–60 Hz)

Voltage

Rating

Peak Inrush

Current, A

Peak

Full-Load

Current, A

Average

Current, A

Charge Time

(sec) ➀

Recommended

Fuse (Slo-Blo)

24 Vdc

21–27 Vdc

30.0

14.0

11.0

3.0 (nom)

12 A, 125 V

48 Vdc

41–53 Vdc

18.0

7.0

4.5

3.0 (nom)

7 A, 125 V

72 Vdc

62–80 Vdc

10.0

4.5

3.0

3.0 (nom)

5 A, 125 V

120 Vac

102–132 Vac

7.5

4.0

2.0

3.0 (nom)

4 A, 125 V

125 Vdc

106–137 Vdc

8.0

2.5

1.8

3.0 (nom)

2.5 A, 125 V

240 Vac

204–264 Vac

6.0

2.5

1.0

3.0 (nom)

2.5 A, 250 V

Charging times apply to nominal voltage only; times may vary at maximum and minimum voltages.

Table 1. Electrical data for the Motor Operator Mechanism.