Trouble-shooting – GE Industrial Solutions Power Break II Motor Operator User Manual
Page 11
Power Break® II Motor Operator Mechanism
Trouble-Shooting
11
Trouble-Shooting
The following guide is provided for trouble-shooting and
isolating common problems. It does not cover every
possible situation. Contact the ED&C Customer Support
Center at 800-843-3742 if any problem is not resolved by
these procedures.
SS
S
S yyyym
m
m
m p
p
p
p tttto
o
o
o m
m
m
m
P
P
P
Po
o
o
ossssssssiiiib
b
b
blllleee
e C
C
C
Caa
a
au
u
u
usssseee
e
C
C
C
Co
o
o
orrrrrrrreee
eccc
cttttiiiivvvveee
e A
A
A
Accc
cttttiiiio
o
o
on
n
n
n
The breaker does not
charge.
The breaker is already
charged.
Power is not available to the
Motor Operator Mechanism.
The breaker was partially
charged manually
None.
Check that the Motor Operator Mechanism is wired
correctly, as shown in Figure 5.
Check that all connectors are properly seated.
Check that the voltage applied to the Motor Operator
Mechanism is within the specified range.
Complete the manual charging cycle until the
breaker’s charge indicator shows CHARGED.