Introduction
Auxiliary Switch:
Auxiliary contacts indicate the position of the
Circuit Breaker main contacts. These contacts
operate simultaneously with the breakers main
contacts. Default breaker configuration consists

of 3 normally open (NO) and 3 normally closed
(NC) contacts. The STD Auxiliary switch (GAUX3R)
can be replaced with any of the following
configurations to increase the number of
available contacts.

• Power rated contacts 8 NO & 8 NC

(GAUX6R)

• Power rated contacts 3 NO & 3 NC plus

Low Signal rated contacts 2 NO & 2 NC
(GAUX5R)

• Power rated contacts 4 NO & 4 NC plus

Low Signal rated contacts 4 NO & 4 NC

(GAUX8R)


See Wiring Diagram on last page for Power Rated
and Low Signal Connections







DEH-41415 Installation Instructions


EntelliGuard

®

G Circuit Breaker


Accessories


Auxiliary Switch




WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation , et décharger les

resorts d’armement

Table 1. Auxiliary switch ratings






DC Ratings*

240V

5A (6 contacts in

series)

125V

10A (3 contacts in

series)

DC

24V 15A

* DC ratings are not UL listed

Note:
The following Aux options are not available when

a Side Mounted Disconnect or Coil Signaling
Contacts are installed in the breaker

• Power rated contacts 4 NO & 4 NC plus

Low Signal rated contacts 4 NO & 4 NC
(GAUX8R)

Power rated contacts 8 NO & 8 NC (GAUX6R)



AC Ratings

220/240V

10A

AC

110/120V

15A

1