3. Install the circuit breaker.

a. Main devices (lugs only on ON side of circuit

breaker). Place the OFF side of the breaker over the

stud posts, as shown in Figure 4. Fasten the breaker

to the module with

1

/

4

-20 x

3

/

4

"

screws with conical

washers and #10-32 x 3

3

/

4

" screws with #10 flat

washers. After all screws are in place, tighten the

1

/

4

-20 screws to 40–50 in-lb and the #10-32 screws to

25–30 in-lb.

b. Branch devices (lugs only on OFF side of the

breaker). Remove the lug cover, if present. Place the

ON side of the breaker over the stud posts, as shown

in Figure 4. Secure the breaker to the module with

1

/

4

-20 x

3

/

4

"

screws with conical washers and #10-32

x 3

3

/

4

" screws with #10 flat washers.

Do not remove

the protective cap or tape from the top portion of

the stud posts unless a breaker is to be installed in

that position. After all screws are in place, tighten

the

1

/

4

-20 screws to 40–50 in-lb and the #10-32

screws to 25–30 in-lb. Replace the lug cover, if

present.

For double-branch devices, repeat this procedure

for the other breaker. Breaker types TFJ, TFK,

THFK, or TFL may be combined and breaker types

SFHA, SFLA, or SFPA may be combined.

4. Position the breaker module. Loosen the latch lock

screws and fully retract the latches. Line up the guide

fingers on both ends of the module with the notches

in the panelboard interior rails, as shown in Figure 5.

Allow no space between units.

Figure 4. Installing the breaker on the module.

Figure 5. Positioning the breaker module.

5. Install the module. Latch one side of the circuit

breaker module. Release the rail latch. Pivot the

module onto the bus bars and engage the second

latch. Release the rail latch. Tighten the rail latch

screws to 25 in-lb, as shown in Figure 6.

Figure 6. Installing the breaker module.

6. Wire the circuits. Refer to the label on the circuit

breaker for the proper tightening torque.

7. Filler plate kits. Install the appropriate filler plate kits,

as listed in Table 1.

Lug

Cover

Stud

Post

1

/

4

-20 Screw &

Conical Washer

#10-32 Screw

& Flat Washer

Filler

Support

Latch Lock

Screw

Latch

Latch Lock

Screw

Latch

Advertising