Geh-5626p3-p4, Attention – procedure for aluminum terminations – GE Industrial Solutions Spectra Series Power Panelboards AMC2FJ, AMC6FLS, AMC3FLS, AMC2FLS User Manual

Page 3

Advertising
background image

Filler Plate

Cat. No.

Module Type

AFP3SFD

AMC6FJ
AMC4FJ

AFP3SFS

AMC3FJ
AMC2FJ

AFP4SFD

AMC6FLS
AMC4FLS

AFP4SFS

AMC3FLS
AMC2FLS

Table 1. Filler plate kit for each breaker module type.

Attention – Procedure for Aluminum
Terminations

1.

Strip the insulation, being careful to not nick the wire.

2.

Clean the wire strands with a wire brush.

3.

Thoroughly coat the stripped conductor with a
suitable antioxidant compound, such as ALNOX or
PENETROX A13.

4.

Insert the conductor and tighten the connector screw
to the indicated torque, as indicated on the rating
label.

Advertising